CLC-10 Comtech LPOD Controller Handheld Terminal M&C Accessory Revision 3
Serial-Based M&C using the CLC-10 MN-CLC10
3–7
3.4.4 Packet Structure
ASCII code 60
ASCII codes 48-57
ASCII code 47
ASCII codes 65-90,
97-122
ASCII codes
61 or 63
ASCII code 13
Example: <0412/MUT=1{CR}
ASCII code 62
0-9
ASCII codes 48-57
ASCII code 47
ASCII codes 65-90,
97-122
ASCII codes
61,63,33 or 42
(From 0 to n
Line Feed
ASCII codes
13,10
Example: >0412/MUT=1{CR}{LF}
3.4.4.1 Start of Packet
Controller-to-Target: This is ‘less-than’ the character '<' (ASCII code 60).
Target-to-Controller: This is the ‘greater-than’ character '>' (ASCII code 62).
Because this is used to provide a reliable indication of the start of packet, these two characters may not appear anywhere else within the
body of the message.
3.4.4.2 Target Address
Up to 9,999 devices can be uniquely addressed. In EIA-232 applications, this value is set to 0. In EIA-485 applications, the permissible
range of values is 1 to 9999.