NetVue IMS Release 1.1 Overview and Introduction Revision 3
NetVue User Guide MN-NETVUE
1–16
1.8.3 Environmental
1.8.3.1 Temperature
Table 1-4 Environmental
Specification
Operating Requirements
Non-Operating Requirements
Temperature Ranges
(for altitude ≤ 900m or 2952.75ft)
10°C to 35°C
(50°F to 95°F)
-40°C to 65°C
(-40°F to 149°F)
Temperature Ranges (-40°F to 149°F)
(for altitude > 900m or 2952.75ft)
10°C to T
1
°C
(50°F to T
2
°F)
Temperature Gradient
(maximum per 60 minutes)
10°C 20°C
1.8.3.2 Humidity
Table 1-5 Humidity
Specification
Operating Requirements
Non-Operating Requirements
Humidity Percent Ranges
(non-condensing)
20% to 80%
(maximum wet bulb temperature = 29°C)
5% to 95%
(maximum wet bulb temperature = 38°C)
Humidity Gradient
(maximum per 60 minutes)
10% 10%
1.8.3.3 Vibration
Table 1-6 Vibration
Maximum Vibration
Operating 0.26 Grms at 5-350 Hz for 15 minutes
Storage 1.88Grms at 10-500 Hz for 15 minutes
1.8.3.4 Shock
Table 1-7 Shock
Maximum Shock
Operating One shock pulse in the positive z-axis (one pulse on each side of the system) of 31G for 2.6ms in the operational
orientation.
Storage Six consecutively executed shock pulses in the positive and negative x, y and z-axes (one pulse on each side of
the system) of 71G for up to 2ms.
Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of
the system) of Half-sine shock 71G for up to 2ms and square-wave shock 32G, 270 in/sec.